K100-U Ultra low leakage energy saving damper

K100‐U Ultra low leakage energy saving volume control damper (Insulated Blades). Blade leakage in accordance with DIN 1946 part4

For more information please contact us.

  • Multi‐leaf dampers primarily used in air conditioning and ventilation systems for volume control, pressure control and isolation
  • This range of dampers are energy saving, reducing air loss considerably over standard products. The K100‐U incorporate insulated blades for improved thermal performance and noise reduction
  • Direct fixing to the inlet louvres to form one assembly
  • Room isolation in manufacture of pharmaceutical products
  • Agricultural stores
  • System sterilization

  • K100‐U ultra low leakage dampers meet the stringent DIN 1946 part 4 standard for blade leakage
  • K100‐U dampers incorporate thermal insulation within the blade section
  • High strength galvanised channel casing
  • Aerofoil section extruded aluminium blade with integral blade edge seal
  • Opposed blade action for optimum air control
  • Full Length 12.7mm square drive shaft
  • Individual blade coupling by plastic gears, running in maintenance free acetal bushes, forming a non ferrous gearing system
  • Manual, electrical or pneumatic control options
  • Large single and multiple module assemblies
  • Circular Spigot or Flanged connections available
  • Face and bypass dampers

  • Casing – 1.2mm thick galvanised mild steel casing, 132mm deep and 40mm flanges c/w 10mm return edge for flange clamps
  • Blades – Aerofoil section extruded aluminium blades, 103mm wide c/w EPDM edge seals. K100‐U blade sections filled with thermal insulation
  • Gears – Plastic gear with integral stub spindle. K100‐U gear fitted with foam/felt side seals running on low friction PTFE strip
  • Bushes – 25mm diameter hard acetal, incorporating locking rib. Bushes encased as standard

  • K100‐U – 100 W x 108 H to 1000 W x 1008 H in a single module
  • For larger multiple module assemblies, please consult our technical department
  • Circular, flat oval, spigot & flanged units are available

  • Temperature: ‐10°C to +90°C
  • Pressure: ± 2500Pa
  • Velocity: up to 20m/s

  • Damper casing materials of 316 grade stainless steel, Aluminium and PVC
  • Dampers incorporating oilite bearings
  • External linkages or gears
  • Parallel bladed dampers
  • Face and bypass dampers
  • Damper casings to suit customer requirements
  • Flange drillings
  • Powder coated casing & blades in either Epoxy or Polyester
  • Concealed Motors

  • M = Manual operated quadrant
  • E = Extended spindle for motorization (by others)

  • Electrical actuator options – 24/110/240 volt units. Double acting /open‐close, modulating, spring return
  • Pneumatic actuator options. Double acting/open‐close, modulating, spring return